1. 0.4 to 10 KV Step Up three phase oil immersed electric power industrial transformer

0.4 to10kv step up three phase oil immersed Power transformer is rated voltage during 6-35kV, oil immersed transformer are most used in power plant,power grid transmission and distribution station,industry& commerce electrical substation as the electrical equipment of power transmission,

(1),Natural cooling or force air or oil cooling,

(2),Two windings or three windings

(3),On-load or no-load voltage tapping changer

(4),capacity range 10-5000kVA

修改后5.jpg

2.  Parameter list

Rated Capacity 

10~2500 KVA

Vector Group

Yyn0 or Dyn11

Impedance Voltage

4%, 4.5%

Frequency

50/60Hz 

Rated voltage H. V

11, 10.5, 10, 6.3, 6KV (or customized)

Rated voltage L.V

0.4, 0.69KV (or customized)

Cooling method

ONAN

Altitude

≤1, 000m 

Tapping range

+/- 5% or +/- 2 * 2.5% (or customized)

Temperature rise limits

Winding ≤ 65K, Top oil ≤ 60K

Highest ambient temperature

+40℃

Lowest temperature

-25℃

Product standard

IEC60076 & GB1094 and GB/T6451

Warranty

2 years

3. Product standard

ISO 1461: Hot dip galvanized coatings on fabricated iron and steel articles – Specifications and test methods.
IEC 60076: Power transformers.
IEC 60044: Instrument transformers.
IEC 60296: Specification for unused mineral insulating oil for transformers and switchgear.
IEC 60354: Loading guide for oil – immersed power transformers.
IEC 60214: Tap-changers - Part 1: Performance requirements and test methods, Part 2: Application guide.
IEC 60512: Connectors for electronic equipment.
4. Routine test

ROUTINE TEST to IEC 60076 (to be done during acceptance testing at factory)
• Measurement of winding resistance
• Ratio test
• Vector group
• Separate source voltage withstand test
• Induced over-voltage
• Insulation resistance
• Oil leakage test on fully assembled transformer for 12 hours
• Measurement of impedance voltage
• Magnetic balance
• Measurement of no-load loss and current
• Measurement of load loss (at normal & extreme taps)
• Tests on on-load tap-changer
• Tests on on-load tap-changer remote control panel
• Efficiency at 50%, 75%, 100% loading at unity p.f and rated terminal voltage (Corrected to 75C)
• Lightning impulse withstand test

 Type Tests to IEC 60076 (to be done during acceptance testing at factory)

• Temperature rise test – To be performed on one unit during acceptance testing.
• Lightning Impulse Withstand Test is already listed under Routine Tests as per IEC 60076.

5. Factory show

公司风采(2).jpg

6. FAQ

(1). How to order?

A: Send the inquiry with your technical data or tell me your application. We can make recommendation. 

(2). What is lead time and shipment?

A: Shipment term is FOB, CIF,DDU, DDP, CIP. Lead time of products is 3-10 days, if special need, L/T is discussed case by case.

(3).How to pay?

A: By T/T, L/C, cash, PayPal, western union, D/P, D/A and others available

(4).What is Warranty?

A: At least two years promise, some products can extend longer.

7. Contact us

XIGAO Electricenergy Group Co.,LTD.

Add.: No. 6, Weibei Industrial Park, Xi'an City, Shaanxi Pro., CN. 710600 

Phone: 0086 13319220197

Email: emma@zgxgdn.com

WhatsApp: 008613319220197

Skype: sunnysunny12271

Wechat: 13319220197

Website:  www.zgxgdn.cn



Inquiry